Product Overview
The GDH-CE180 through GDH-CE288 High Temp Ceiling Mounted series is an industrial dehumidifier engineered for concealed overhead installation in high-temperature production environments — 5 to 60 °C continuous operating range, against the 5 to 38 °C envelope of standard industrial equipment. Three capacity tiers from 180 to 288 L/day cover small to mid-sized processing rooms across food drying, pharmaceutical GMP suites, electronics workshops, and light-industrial heat-treatment areas where humidity control must continue at elevated ambient temperatures and floor real estate is committed to production equipment.

Why ceiling mounting plus high-temp engineering matters
Two problems converge in modern industrial workshops. First, standard industrial dehumidifiers rated to 38 °C shut down on thermal protection above their envelope — exactly during peak-load hours where humidity control matters most for food processing lines, drying rooms, and GMP suites. Second, floor-standing equipment occupies square meters that production lines, packaging machinery, and forklift lanes need. The High Temp Ceiling Mounted series solves both: higher-pressure-rated compressors, larger condenser heat exchange surface, and industrial-grade electronic components extend the operating envelope to 60 °C, while the concealed ceiling installation reclaims 100 % of usable floor space and distributes dry air uniformly through the treated zone.

Shared build points (all three models)

  • 5 to 60 °C operating temperature envelope — sustained high-temperature operation
  • Concealed ceiling installation — zero floor footprint
  • All-copper condenser and evaporator coils
  • R32 refrigerant — selectable at order
  • 30 – 80 % RH working humidity range with precision sensor
  • Continuous hose drainage via gravity — no internal water tank
  • Automatic hot-gas defrost system
  • High-efficiency rotary fan with high static pressure for ducted distribution
  • Thickened moisture-proof sheet metal cabinet, corrosion-treated internals
  • 380V / 50Hz three-phase power on all three models
  • Wall-mounted wired LCD controller with fault self-protection codes
  • OEM/ODM supported — MOQ 10 units per model

For higher-capacity ceiling-mounted installations from 380 to 720 L/day, see the High Temp Ceiling Mounted Industrial Dehumidifier (GDH-CE380 / CE480 / CE600 / CE720). For floor-standing installations with the same wide temperature envelope, see the Temperature-Controlled Floor-Standing Industrial Dehumidifier (GDH-180E to GDH-1440E). For standard 5 to 38 °C operating range in clean industrial environments (warehouses, archives, workshops, basements), see the standard industrial dehumidifier series. For corrosive industrial atmospheres (pools, marine, chemical), see the industrial swimming pool dehumidifier. For sustained operation below 5 °C ambient, switch to the desiccant dehumidifier.

Technial Parameters

High-Temp Ceiling-Mounted Range (GDH-CE180 / CE240 / CE288)

SpecificationGDH-CE180GDH-CE240GDH-CE288
Dehumidification Capacity (30°C / 80% RH)180 L/day240 L/day288 L/day
Power Supply380V / 50Hz380V / 50Hz380V / 50Hz
Rated Power2800 W3000 W3400 W
Noise Level≤60 dB(A)≤60 dB(A)≤60 dB(A)
Airflow2200 m³/h2400 m³/h2400 m³/h
Working Humidity Range30% – 80% RH30% – 80% RH30% – 80% RH
Recommended Coverage Area180 – 240 m²200 – 300 m²260 – 350 m²
Working Temperature5 – 60 °C5 – 60 °C5 – 60 °C
Drainage MethodContinuous Drainage (Drain Hose)Continuous Drainage (Drain Hose)Continuous Drainage (Drain Hose)
Product Dimensions (L × W × H)950 × 600 × 700 mm950 × 600 × 700 mm1000 × 800 × 700 mm
Packing Dimensions1000 × 650 × 760 mm1000 × 650 × 760 mm1100 × 860 × 780 mm
RefrigerantR410A / 1200 gR410A / 1500 gR410A / 1500 g
Net / Gross Weight70 / 75 kg80 / 85 kg80 / 85 kg

Product Details

Where the GDH-CE180 to GDH-CE288 Series Fits Best

The applicable scenarios on the product specification — food processing and drying rooms, pharmaceutical and GMP workshops, precision electronics and semiconductor assembly, industrial heat treatment and metallurgy, chemical industry, energy facilities, and wood and furniture manufacturing — share two operational characteristics: ambient temperatures reach or exceed 40 °C during process operation where standard 5 to 38 °C industrial equipment would shut down on thermal protection, and every square meter of floor is committed to production activity, making ceiling-mounted format the only practical installation option.

This is not a general-purpose warehouse dehumidifier. For warehouses, archives, basements, switchgear rooms, and similar clean industrial spaces operating at 15 to 30 °C ambient year-round, the standard industrial dehumidifier range serves at lower cost. The GDH-CE180 to GDH-CE288 series adds value in mid-sized precision processing rooms with elevated ambient temperature: food curing chambers running 35 to 50 °C, pharmaceutical granulation and drying suites at 30 to 50 °C, tempering and heat-treatment zones between 40 and 55 °C, and semiconductor bake-out or reflow-adjacent areas from 40 to 55 °C. For rooms above roughly 350 m² or where 5-60°C operation is required at higher airflow / higher capacity, step up to the GDH-CE380 to GDH-CE720 high-capacity ceiling-mounted range.

The 5 to 60 °C Envelope — What Makes the Wide Range Work

Achieving 60 °C sustained operation reliably requires specific engineering choices in the refrigeration circuit, control electronics, and structural components. Standard industrial dehumidifiers use commercial-grade compressors, standard fin-tube heat exchangers, and PCB-mounted electronics rated to 70 °C junction temperature — all of which exceed their design envelope somewhere between 40 and 45 °C ambient, triggering high-pressure cut-out or thermal protection shutdown. The GDH-CE180 to GDH-CE288 series uses higher-pressure-rated compressor specifications designed for elevated condenser saturation pressure, larger condenser heat exchange surface to maintain pressure differential at high ambient, industrial-grade electronic components rated to 85 °C+ junction temperature, and enhanced internal airflow paths for compressor and motor cooling. Sustained operation at 50 to 60 °C ambient is the design point — equipment that standard industrial dehumidifier models would shut down on within minutes runs continuously here.

Concealed Ceiling Installation — How the Ducted Format Works

Each unit installs above the treated zone's ceiling structure or inside a plenum void, with process air ducted from a return grille at the warmest zone (typically ceiling level, where hot humid air stratifies) through the evaporator coil and back to the room through a supply grille. Gravity drainage handles condensate through a continuous drain hose routed to the facility's plumbing lines — the elevated installation position eliminates the need for condensate pumps in most layouts.

The wall-mounted wired LCD controller connects to the concealed unit via a low-voltage signal cable, positioning humidity setpoint adjustment, timer scheduling, and fault code display at ground level for operator access. Standard hot-gas defrost with a high-efficiency rotary fan handles the elevated static pressure of ducted installation, delivering rated airflow through the return-supply duct network without oversizing the fan.

Three Capacity Tiers — Small to Mid-Sized Processing Rooms

Fine-grained capacity structure across the 180 to 288 L/day range, sized to cover the typical footprint of individual production rooms and processing bays:

  • GDH-CE180 (180 L/day, 180 – 240 m²) — individual food drying rooms, single pharmaceutical granulation suites, small metallurgy tempering bays, semiconductor bake-out chambers, wood-drying kilns
  • GDH-CE240 (240 L/day, 200 – 300 m²) — mid-sized pharmaceutical production rooms, food processing lines with adjacent packaging, electronics assembly bays with reflow ovens, mid-sized wood or furniture drying rooms
  • GDH-CE288 (288 L/day, 260 – 350 m²) — larger single-room installations, multi-station pharmaceutical production suites, mid-sized food drying facilities, industrial heat-treatment shops

For installations exceeding 350 m² per zone, either deploy multiple units in parallel for even coverage and built-in redundancy, or step up to the higher-capacity GDH-CE380 to GDH-CE720 tier which covers 350 to 900 m² per single unit.

Application: Food Processing and Drying Rooms

Food processing operations combine two humidity requirements that ordinary equipment cannot meet together: elevated ambient temperature (drying rooms and curing chambers typically operate at 30 to 50 °C) and tight RH control (dry-cured meat rooms hold 65 to 75 % RH, food powder drying suites 35 to 45 % RH, hard-cheese aging caves 80 to 90 % RH). Standard industrial equipment stalls above 38 °C ambient — exactly during the peak production shifts where humidity control matters most.

The GDH-CE180 to GDH-CE288 range serves these processes across the elevated-temperature production window:

  • Meat curing and dry-aging rooms — sustained 12 to 20 °C at 65 to 80 % RH; the wide envelope handles seasonal startup from ambient to setpoint plus emergency operation during HVAC failure
  • Bakery proofing and cooling rooms — 25 to 35 °C at controlled RH for dough consistency and product shelf life
  • Food powder and granulation processing — 35 to 45 °C ambient with tight RH control preventing agglomeration
  • Vegetable and fruit drying — 40 to 55 °C ambient at gradient-controlled RH
  • Fish and seafood drying — 25 to 35 °C at 55 to 70 % RH

For food storage warehouses and cold-chain facilities operating in the standard temperature range, the standard industrial dehumidifier range serves at lower cost.

Application: Pharmaceutical GMP Workshops

A pharmaceutical dehumidifier operates under specific regulatory frameworks — USP <1116> for microbial control in pharmaceutical compounding, EU GMP Annex 1 for sterile manufacturing, and ICH Q7 for active pharmaceutical ingredient production. These specify humidity ranges from 30 to 60 % RH depending on the production stage, held within ±5 % RH stability tolerance.

Many pharmaceutical processes operate at elevated ambient temperatures where the standard 5 to 38 °C envelope of ordinary dehumidifiers is insufficient:

  • Fluid bed drying suites — ambient air around the equipment 35 to 50 °C
  • Granulation with vacuum drying — 40 to 55 °C in the production room
  • Spray drying suites — ambient up to 50 to 70 °C in the immediate equipment area
  • Depyrogenation and glass-wash areas — adjacent zones 40 to 50 °C

The GDH-CE180 to GDH-CE288 range handles the elevated-temperature production areas at mid-sized capacity. For pharmaceutical bulk-production floors above 350 m² per single zone, step up to the GDH-CE380 to GDH-CE720 tier. For room-temperature pharmaceutical environments (capsule filling, packaging, finished goods storage), the standard industrial dehumidifier range is the appropriate sizing.

Application: Precision Electronics and Semiconductor Assembly

Electronics manufacturing operates at variable ambient temperatures across the production sequence, with elevated-temperature zones where standard industrial dehumidifier equipment cannot run continuously: reflow soldering areas at 40 to 50 °C during process operation, burn-in test rooms at 50 to 60 °C for accelerated life testing, PCB curing and bake-out at 40 to 55 °C, and final inspection under sustained lighting heat load. The IPC J-STD-033 standard for moisture-sensitive component handling sets specific humidity targets that this equipment maintains across the variable ambient conditions of electronics production.

For sub-1 % RH dry rooms in semiconductor cleanroom fabrication and lithium-battery cell assembly, desiccant rotary dehumidification is the required technology — see the rotary dehumidifier range. The GDH-CE180 to GDH-CE288 refrigerant-cycle series serves the adjacent supporting zones and higher-humidity electronics areas up to 60 °C ambient.

Application: Industrial Heat Treatment and Metallurgy

Heat-treatment operations — annealing, tempering, quenching, case-hardening — produce ambient temperatures in adjacent processing areas from 40 to 60 °C during peak operation, alongside high moisture loads from quenching oils and cooling fluids. Uncontrolled humidity in these zones drives condensation on newly cooled metal parts, causing surface oxidation and rust formation between processing stations. The GDH-CE180 to GDH-CE288 range maintains dry-air conditions at ambient temperatures where standard equipment cannot operate:

  • Tempering-oven adjacent zones — 40 to 55 °C at controlled RH
  • Quenching stations and cooling lines — 25 to 40 °C, high moisture load
  • Post-treatment inspection and finishing rooms — 25 to 35 °C, condensation control critical
  • Foundry and casting cleanup zones — 30 to 50 °C, mixed moisture and particulate loads

Application: Chemical Industry and Energy Facilities

Chemical processing plants and energy facilities operate mixed-temperature production zones with humidity control requirements dictated by the chemistry involved: 30 to 45 % RH for hygroscopic reagent handling, 40 to 55 % RH for general process areas, and controlled dewpoint for battery electrolyte assembly and fuel-cell membrane handling. Standard industrial dehumidifier equipment is limited to the 5 to 38 °C envelope; the GDH-CE180 to GDH-CE288 range extends operation to the 40 to 60 °C conditions common in reactor rooms, extrusion adjacent zones, and battery formation cycling areas.

Application: Wood and Furniture Manufacturing

Wood-drying kilns operate at 35 to 60 °C with programmed RH ramp cycles that reduce moisture content in green lumber from ~30 % to ~8 % over multi-day drying schedules. Furniture and wood-product finishing rooms hold 40 to 55 % RH at 20 to 30 °C to prevent joint failure and surface finish defects. The GDH-CE180 to GDH-CE288 range serves the elevated-temperature drying processes and the post-drying conditioning zones — sizing typically matches one unit per kiln or per finishing bay.

R32 Refrigerant — Standard Charge, Regulated-Market Compliance

All three models use R32 refrigerant (HFC single-component, GWP 675, A2L mildly flammable) with factory-sealed circuits as the standard configuration. R32 is the established compliance choice across regulated global markets — EU under the revised F-gas Regulation (EU 2024/573), UK, Japan under the Fluorocarbons Emissions Control Law, Australia, and increasingly across North America, China, and other markets phasing out legacy HFC blends. Single-component composition eliminates the fractionation risk associated with blended refrigerants during charge and top-up service — a meaningful maintenance advantage for precision equipment operating on multi-year service cycles in mission-critical cleanroom, pharmaceutical, and data center installations. R32 charge volumes are compact — below the IEC 60335-2-40 charge limits for the installation category, with exact charge specified per model in the technical documentation package provided at order. For facility safety policies that require additional ventilation analysis for A2L refrigerant in confined cleanroom or laboratory installations, we provide the charge and ventilation reference data required for the assessment.

For facility safety standards that specifically prohibit any flammable refrigerant in occupied production areas — a policy still applied in certain pharmaceutical validated cleanrooms, sterile manufacturing suites, and legacy-specification data centers — R410A is available as an ODM configuration from MOQ 200 units. R410A (HFC blend, GWP 2088, non-flammable) remains a valid selection where facility policy overrides GWP considerations, though it is under phase-down schedules across the EU, UK, US, and other regulated markets — most new-build projects specify R32 or absorb the safety analysis needed to permit R32 in occupied spaces to align with 2027–2032 regulatory milestones.

Compressor-Cycle Refrigeration with All-Copper Coils

All three models use sealed compressor refrigeration cycles with all-copper evaporator and condenser coils. Copper construction provides better thermal conductivity than aluminum-tube assemblies — important for maintaining extraction performance across the wide 5 to 60 °C envelope where coil temperature differentials change significantly with ambient. The hydrophilic fin coating accelerates condensate runoff from the evaporator surface, which matters in high-humidity precision environments where standing water would create bacterial growth conditions inappropriate for pharmaceutical and food processing applications. Each unit includes the standard protection set plus enhancements specific to wide-envelope operation: high-pressure cut-out with extended trip threshold, enhanced hot-gas bypass defrost, overcurrent protection on each phase, compressor thermal cut-out, and phase-loss detection.

Ceiling-Mounted Installation Requirements

Concealed ceiling installation requires structural attachment points capable of supporting 70 to 85 kg per unit plus dynamic load from operation, adequate plenum access clearance for filter and coil maintenance (typically 600 mm minimum clearance above and beside the unit), continuous condensate drainage routed through a slope of at least 1:100 to the plumbing endpoint, and 380V / 50Hz three-phase electrical service to the installation location. Return-air and supply-air ducting matched to the rated airflow (2200 – 2400 m³/h) and rated external static pressure. For retrofit installations in existing buildings, gravity drainage may require adding a condensate lift pump if the plumbing endpoint sits above the unit — quoted per project.

OEM and ODM Service

As a Chinese industrial dehumidifier manufacturer with full-spectrum OEM and ODM capabilities for the High Temp Ceiling Mounted range, we support brand customization from MOQ 10 units per model. OEM scope covers branding, cabinet color (standard white or gray finish typical for concealed installations, any RAL or Pantone for visible surfaces available), plug type or terminal block configuration for the destination market's electrical standard, control firmware language, and packaging artwork.

ODM scope covers refrigerant selection (R32 from MOQ 200), BMS integration (Modbus RTU from MOQ 50, BACnet/KNX from MOQ 200), control firmware customization for facility-specific automation, humidity sensor calibration certificates for regulatory compliance documentation, IQ/OQ documentation packages for pharmaceutical applications (quoted per project), and certification routing (CE, RoHS, ETL, SAA, GS depending on target market). Production lead time 25 to 40 days after artwork sign-off. FOB Ningbo or Shanghai.

For other capacity tiers and installation formats, browse the full commercial dehumidifier lineup.

FAQs

How does the GDH-CE180 to GDH-CE288 series differ from the higher-capacity GDH-CE380 to GDH-CE720 range?

Same product line and same 5 to 60 °C thermal engineering — different capacity tier. The GDH-CE180 to GDH-CE288 range covers small to mid-sized processing rooms from 180 to 350 m² per single unit at 180 to 288 L/day extraction. The GDH-CE380 to GDH-CE720 range extends coverage to 350 to 900 m² per unit at 380 to 720 L/day for larger production halls, mega-warehouses adjacent to processing lines, and full pharmaceutical bulk-production floors. Choose the tier by treated zone area, moisture load calculation, and whether the room's peak ambient conditions require additional headroom. For installations exceeding 900 m² or with continuous high moisture loads, distributed multi-unit deployment across either tier typically outperforms oversizing a single point.

What makes the 5 to 60 °C envelope possible — what is engineered differently versus a standard ceiling-mounted dehumidifier?

Four engineering differences from standard ceiling-mounted equipment. First, the compressor is specified for higher condenser saturation pressure to handle the 60 °C upper ambient — standard compressors fail on high-pressure cutout above 40 to 45 °C ambient because the condenser cannot reject heat fast enough at standard surface area. Second, the condenser heat exchanger has larger fin surface area to maintain pressure differential at high ambient. Third, the control PCB and motor controller use industrial-grade electronics rated to 85 °C+ junction temperature versus commercial-grade boards rated to 70 °C — necessary for sustained operation in 60 °C plenum ambient temperature. Fourth, the internal airflow paths route cooling air past the compressor and control electronics separately from the process-air stream, preventing hot process air from exceeding component temperature limits.

What are the ceiling-mounted installation requirements and mechanical clearances?

Each unit weighs 70 to 85 kg — the ceiling structure requires attachment points rated for the unit weight plus operational dynamic load and any duct assembly. Standard drop-ceiling grid is not sufficient; attach directly to structural beams or purpose-installed suspension frames. Plenum access clearance of 600 mm minimum above and beside the unit is required for filter changes, coil inspection, and condensate line maintenance. Ducted return and supply grilles must handle 2200 to 2400 m³/h at the rated external static pressure. Facility electrical service to the installation location: 380V/50Hz three-phase at rated power (2.8 to 3.4 kW per unit). Condensate drainage routed through a slope of at least 1:100 to the plumbing endpoint. For retrofit installations where gravity drainage isn't feasible, a condensate lift pump can be added — quoted per project.

Is this dehumidifier for pharmaceutical industry GMP-compliant, and what validation documentation is available?

GMP-compliance is a facility certification, not an equipment certification — the equipment supports compliance, the facility achieves it through validated installation, operation, and ongoing monitoring. For pharmaceutical industry installations, we provide: humidity sensor calibration certificates traceable to national standards, certificate of conformity for the unit specifications, IQ/OQ (Installation Qualification / Operational Qualification) documentation packages as an ODM addition quoted per project, and PQ (Performance Qualification) protocol templates for the buyer's validation team to execute on site. EU GMP Annex 1, USP <1116>, and ICH Q7 compliance are achieved through the buyer's validated installation process using equipment specified to meet the facility's documented humidity targets.

How is condensate managed when the unit is mounted overhead in a concealed ceiling plenum?

Ceiling-mounted installation position enables efficient gravity drainage in most facility layouts. Condensate collects in a sloped internal pan and flows continuously through a heavy-walled drain hose routed to the facility's plumbing lines — no manual water emptying required. The drain hose must maintain a slope of at least 1:100 downstream of the unit, and the endpoint must sit below the unit's drain outlet by at least 100 mm to allow the P-trap or air-break to function. For retrofit installations where the plumbing endpoint sits above the unit's drain outlet, a condensate lift pump is added at the drain outlet — this configuration is straightforward and adds minimal cost.

What is your MOQ and lead time for OEM/ODM orders?

OEM MOQ is 10 units per model — branding, cabinet color, plug type or terminal block configuration, packaging artwork. ODM specifications: R32 refrigerant from MOQ 200, 460V/60Hz North American specification from MOQ 50, BMS integration via Modbus RTU from MOQ 50, BACnet/KNX from MOQ 200, IQ/OQ documentation packages for pharmaceutical applications quoted per project. Production lead time 25 to 40 days after artwork sign-off, covering sheet metal fabrication, anti-corrosion coil treatment, refrigeration circuit pressure testing, and full electrical calibration. Shipping FOB Ningbo or Shanghai. Standard certifications include CE and RoHS; ETL, SAA, GS, UL and other regional marks available with timeline impact.

Specifying for a high-temperature industrial application? Send us the facility layout (treated zone dimensions, ceiling height, plenum space, structural attachment type), ambient temperature profile across processes and shifts (peak high, sustained high, duration), target RH and stability tolerance, regulatory framework if applicable (GMP, HACCP, ISO 14644 cleanroom class), electrical infrastructure at the installation position, condensate drainage endpoint location, and BMS integration requirements. Our application engineering team will confirm the correct capacity tier or recommend a distributed multi-unit configuration, refrigerant selection R32 for your market), BMS integration approach, and validation documentation package if needed. For higher-capacity ceiling-mounted installations, see the GDH-CE380 to GDH-CE720 range. For floor-standing installations, see the GDH-180E to GDH-1440E series. For standard 5 to 38 °C operating range at lower cost, see the standard industrial dehumidifier range. Quotation within one working day, with technical drawings, extraction curves across the temperature envelope, and certification documents available before order confirmation.